Steel Hoarding Panel Connections: Which Test Evidence to Request

Ask for evidence that covers the sheet fixing, the frame joints and the support arrangement in the submitted drawing. A test on an individual fastener answers a different question from a test on an assembled bay.

Joints Carry the Wind

A solid temporary hoarding presents a continuous face to the wind. The pressure on that face is collected by the sheet, passed to the frame through screws, rivets or spot welds, carried along the frame through welded or bolted joints, handed from panel to panel and from panel to post by connectors, and finally delivered to the ground.

Load on a Sheet Fastener

Each fastener holding the sheet to the frame carries the wind pressure on its tributary area, the area of sheet nearer to it than to any other fastener.

Under pressure toward the frame the sheet bears directly on the rails and the fasteners are unloaded. Under suction, on the leeward face or when the wind reverses, the fasteners carry the whole load in tension.

Fastener Retention

ModeDescription
Pull-over (pull-through)The sheet tears round the fastener head and lifts off, leaving the fastener in the frame
Pull-outThe fastener is drawn out of the frame member
Fastener tension or shear fractureThe fastener breaks
Sheet bearing and tearing in shearThe hole elongates and tears toward the sheet edge

Weld Shear

Where sheet is attached by resistance spot welds, each weld acts in shear when the sheet works with the frame, and in tension under suction.

TestResult
Chisel or peel testA sound weld pulls a button of metal from one sheet; a cold weld separates cleanly at the interface
Lap-shear testMaximum force and failure mode; compared with the required shear resistance
Cross-tension testTension resistance of the weld
Visual and fillet gauge, frame weldsWeld present all round; size as drawing; no cracks or burn-through
Macro section, frame weldsFusion into both walls

Connections Between Panels and to the Ground

Anchors deserve separate mention because their capacity depends on the ground, which the manufacturer does not control.

ConnectionTypical failure modes
Panel-to-panel coupler or boltSlip; bolt loosening; bracket bending; gap opening
Panel to post (socket, bracket or bolts)Bolt shear; bearing and tear-out in thin frame wall; bracket weld failure
Back-stay to panel and to ballast or anchorPin shear; lug weld failure; buckling of stay; pin loss
Post to base plateWeld cracking at base; plate bending
Base to ground (anchors, pins, counterweights)Anchor pull-out; sliding of ballast

Choosing the Test for Each Joint

Component tests, such as fastener pull tests and weld lap-shear tests, give numbers for design and for process control. A proof load on an assembled bay, applied as a distributed or multi-point load to the face and reacted through the real supports, shows whether the joints work together and reveals the weakest link.

Reading the Failure

Ductile, distributed failure, such as sheet bearing, hole elongation or visible bending of a bracket, gives warning and allows load to be shared between fasteners. It is the preferred mode.

Brittle or progressive failure, such as spot-weld interface fracture, thread stripping or pull-over that passes from one fastener to the next, gives no warning and can unzip a whole line. Joints that fail this way need a larger margin and closer inspection.

The way a test specimen fails is as informative as the load at which it fails.

Scatter: a wide spread of results from nominally identical joints points to an uncontrolled process, usually weld settings or fastener installation, and is a finding in itself.

Acceptance and Records

Records: test results with failure modes, material batches, machine settings and inspector, traceable to the panel lot.

Type testing: fastener pull-over and pull-out, weld lap-shear, and a proof load on an assembled bay, for each combination of sheet, frame and connector.

Installation: count of fasteners and connectors against the drawing; torque or setting check on a sample; proof test of anchors.

Sharp Edges

HazardWhere
Sheet edgesPanel perimeter if not folded or capped; sheet ends at laps
Tube ends and bracketsPosts, stays, frames
Exposed fastener pointsScrew tips through the back of frames

Match each test to a revision on the order

A fastener report may identify a sample built with a different washer or support spacing. Record the difference in a submission log and ask the supplier to explain the applicability to the new drawing. Hand the verified drawing and evidence references to receiving inspection together.

Frequently asked questions

What should a steel hoarding connection report identify?

Request the tested panel, fasteners, washer arrangement, support spacing and test setup, with enough detail to compare them with the proposed bay.

Can a fastener's catalogue rating be used to approve a complete hoarding bay?

Use the rating as one input. Obtain evidence for the assembled connection and the approval of the proposed support and fixings for the site.